Evaluation of a High-Efficiency, Filter-Bank System



Back to list of publications

Title:Evaluation of a High-Efficiency, Filter-Bank System
Author:Stephen B. Martin Jr., Bryan R. Beamer, and Ernest S. Moyer
Date of Publication:2006
Hyperlink:http://www.tandfonline.com/doi/abs/10.1080/15459620600584378
Product:1108
Abstract:

National Institute for Occupational Safety and Health (NIOSH) investigators evaluated filtration efficiencies at three U.S. Postal Service (USPS) facilities. Ventilation and filtration systems (VFSs) had been installed after the 2001 bioterrorist attacks when the USPS unknowingly processed letters laden with B. anthracis spores. The new VFS units included high-efficiency particulate air (HEPA) filters and were required by USPS contract specifications to provide an overall filtration efficiency of at least 99.97% for particles between 0.3 μm and 3.0 μ m. The USPS evaluation involved a modification of methodology used to test total filtration system efficiency in agricultural tractor cab enclosures. The modified sampling strategy not only proved effective for monitoring the total filtration system component of VFS performance but also distinguished between filtration systems performing to the high USPS performance criteria and those needing repair or replacement. The results clearly showed the importance of choosing a pair of optical particle counters that have been closely matched immediately prior to testing. The modified methodology is readily adaptable to any workplace wishing to evaluate air filtration systems, including high-efficiency systems.

Copyright 2012 by Grimm Aerosol Technik GmbH & Co. KG版本说明 联系经销商登录 GTCDS